3.0 Installation
DC Wiring (continued)
DC Grounding
The inverter's chassis grounding lug is used to connect the chassis of the inverter
to the DC grounding system. The terminal accepts wires from #14 AWG to
#2 AWG.
Connect the negative (–) terminal of the battery bank to an appropriately sized
conductor and connect it to a solid earth ground, such as a grounding rod, driven
6–8 feet into the earth. Xantrex DC disconnects include a grounding block for the
DC negative to simplify grounding. This procedure will properly ground the DC
circuits.