Superheat controller and stepper valve driver, Type EKE 1A, 1B, 1C, 1D
6.2.3 O setting Superheat, Temperature and OD Via External signal
Temperature and superheat references can be displaced in positive or negative direction using a current signal
(EKE1C only), voltage signal or via Modbus.
Table 33: O setting Superheat, Temperature and OD Via External signal
EKE
O set via External current
signal
O set via Voltage current sig‐
nal
O set via Bus
Figure 62: O setting Superheat, Temperature and OD Via External signal
Offset
R006
Ext. ref offset max.
5
R106
Ext. ref offset min
0
I034
Ext ref. voltage low
NOTE:
O set can be done in positive and negative direction. Extra care must be taken while doing this setting.
Table 34: O setting references for EKE 1A
Parameter
Function
I021
AI4 Con guration
R106
Ext. ref o set min.
R006
Ext. ref o set max
O089
Ext ref. supply
I034
Ext ref voltage low
I035
Ext ref. voltage high
Table 35: O setting references for EKE 1B, 1D
Parameter
Function
I021
AI4 Con guration
R106
Ext. ref o set min.
R006
Ext. ref o set max
O089
Ext ref. supply
I034
Ext ref voltage low
I035
Ext ref. voltage high
© Danfoss | Climate Solutions | 2024.08
1A
1B
-
-
-
R006
Ext. ref offset max.
Voltage
10
I035
R106
Ext ref. voltage high
Ext. ref offset min
Description
Ext. reference
This setting determines how large the o set is when input signal is at min.
This setting determines how large the o set is when input signal is at max.
De ne how the external reference signal is used
0 = V->SH: Displacement of SH reference given by External voltage signal.
1 = V->Temp: Displacement of temperature given External voltage signal.
De ne min. reference Voltage
De ne max. reference Voltage
Description
Ext. reference
This setting determines how large the o set is when input signal is at min.
This setting determines how large the o set is when input signal is at max.
De ne how the external reference signal is used
1 = V->SH: Displacement of SH reference given by External voltage signal.
3 = V->Temp: Displacement of temperature given External voltage signal.
4 = Bus -> SH: Displacement of SH reference given via Modbus.
6 = Bus -> T: Displacement of temperature given via Modbus
De ne min. reference Voltage
De ne max. reference Voltage
1C
Offset
4
I036
Ext ref. current low
4
-2
Ext ref. current hig h
BC398828796060en-000103 | 48
1D
-
Current
20
I037
Need help?