Superheat controller and stepper valve driver, Type EKE 1A, 1B, 1C, 1D
• EKE must be powered up before starting programming.
• To guarantee a reliable USB connection to a host device (e.g., industrial PC), you must: keep USB cable length < 1
m.
• When programming with koolprog if there is any error with values set then EKE will go to factory defualt settings
after restart. Make sure values entered are within range spec ed for each parameter.
Figure 36: koolprog to EKE 1x
• Create your own con guration les on your PC without
having to connect a controller
• Import a parameter con guration le to your PC from a
connected controller. Save the le and download it to
other controllers of the same model
• Select the most frequently used parameters as your fa-
vorites
• Find all the technical documentation for each controller
model within one location
4.2.1 Setting Up KoolProg
KoolProg software supports wide range of Danfoss product, so rst you need to select the EKE 1x series from the
preferences.
Figure 37: Setting Up KoolProg
Then if you want to setup, click the set parameter and select a new project
© Danfoss | Climate Solutions | 2024.08
• Quickly program one. or multiple controllers
by using the progress and completion status
indicators
• Quickly analyze controller behavior and program
patterns by using the graphical trending tool
• Make Online changes to parameter con gurations
• Monitor live status of inputs and outputs
BC398828796060en-000103 | 32