Danfoss EKE 347 User Manual

Danfoss EKE 347 User Manual

Level controller
Hide thumbs Also See for EKE 347:

Advertisement

User Guide
Liquid level controller

Features

© Danfoss | DCS (ADAP-KOOL®) | 2016-04
Liquid level control
Alarm if the set alarm limits are exceeded
Relay outputs for upper and lower level lim-
its and for alarm level
User friendly and easy setup Wizard for first
time configuration
PI control
Low or High side control
When AKV/A is selected, a MASTER/SLAVE
system can run up to 3 AKV/A with distrib-
uted Opening Degree
Manual control of output
The EKE 347 controller is used for regulation of
the liquid level in:
• Pump reservoirs
• Separators
• Intermediate coolers
• Economisers
• Condensers
• Receivers
The controller is communicating with a
transmitter that continuously measures the
liquid level in the actual reservoir.
By comparing the measured value with the
level setpoint entered by the customer, the
controller dictates the valve to increase or de-
crease the liquid flow to or from the reservoir.
Limitation of Opening degree possible
ON/OFF operation with hysteresis
Programming menu with 3 access levels
and separate passwords
Connection to other EKE 347 controllers
possible
Wired remote display possible
BUS communication:
- CAN Bus (Danfoss internal only)
- MODBUS RTU RS485 for communica-
tion with e.g. PLC
DKRCI.PD.RP0.A4.02 | 1

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss EKE 347

  • Page 1 User Guide Liquid level controller EKE 347 The EKE 347 controller is used for regulation of the liquid level in: • Pump reservoirs • Separators • Intermediate coolers • Economisers • Condensers • Receivers The controller is communicating with a transmitter that continuously measures the liquid level in the actual reservoir.
  • Page 2 ICAD AKV/A AKVA or AKV are pulse-width modulating expansion valves. MODBUS communication EKE 347 include as standard RS 485 based MOD- EKE 347 BUS-RTU bus communication interface to third Slave party equipment like PLC.
  • Page 3 User Guide | Liquid level controller, EKE 347 Application examples Pump reservoir Modulating control of injection for a more stable liquid level and suction pressure. System configuration ICAD AKS 4100/ Regulating principle: Low AKS 4100U Level Signal setup: AKS 4100/U...
  • Page 4 User Guide | Liquid level controller, EKE 347 Control Panel Back Press and hold = Log Out Scroll up Home Image Scroll down Enter Press and hold = Log In The user interface of the control panel consists The figure shows the Home display image, which of a multiline display and 4 individual push give the actual overview.
  • Page 5 User Guide | Liquid level controller, EKE 347 Menus Status menu To enter Status menu from Home image: Push once. The Status menu is an open menu accessible for all. Therefore only 1 parameter can be changed from here. A selection of other parameters can be seen from the status menu.
  • Page 6 User Guide | Liquid level controller, EKE 347 Setup & service menu - COMMISSIONING Default Parameter Options values Reference Main switch On, Off Liquid level setpoint 0 - 100% 50.0% Operation mode Master, IO, Slave Master Alarm setup Lower level limit...
  • Page 7 User Guide | Liquid level controller, EKE 347 Setup & service menu - COMMISSIONING (Continued) Default Parameter Options values Service Controller state Actual level Actual referrence Actual OD Actual valve position Digital input status Actual level signal voltage Actual level signal current...
  • Page 8 User Guide | Liquid level controller, EKE 347 Ordering Type Description Code No. EKE 347 Liquid level controller 080G5000 MMIGRS2 Remote display, Panel, S 080G0294 080G0075 Wire for display unit, L = 1.5 m, 1 pcs. 080G0076 Wire for display unit, L = 3 m, 1 pcs.
  • Page 9 User Guide | Liquid level controller, EKE 347 Connection Necessary connections Terminals: 28-29 Supply voltage 24 V a.c. or d.c. 23-24 Expansion valve type: ICM with ICAD Signal from level transmitter type 13-14 Switch function for start/stop of AKS 4100/4100U or controller.
  • Page 10 User Guide | Liquid level controller, EKE 347 Connections - Upper level Upper level AKS 41 Connections 24 V DC 24 V AC upper level AKS 4100/4100U ICAD 1 yellow 4-20 mA ICAD/ICM blue ICAD 2 orange feedback blue –...
  • Page 11 User Guide | Liquid level controller, EKE 347 Connections - Lower level Lower level Connections lower level Common High Level Alarm Normally Open or Normally Open or Normally Closed Normally Closed AKV/AKVA Note: AKV(A) Coil voltage must be the same...
  • Page 12 User Guide | Liquid level controller, EKE 347 EKE 347 - ON/OFF Application. Open/Close solenoid valve with coil 24 V - 230V Voltage: 24 - 230 V a.c. POWER SUPPLY Connection examples AKS 4100/ AKS 41/ AKS 4100/ AKS 4100U...
  • Page 13 User Guide | Liquid level controller, EKE 347 MASTER / SLAVE configuration SLAVE 1 MASTER SLAVE 2 AKVA AKVA AKVA (ICAD) (ICAD) (ICAD) 15 16 17 18 15 16 17 18 15 16 17 18 AKS 4100/ AKS 4100U When more controllers are...
  • Page 14 User Guide | Liquid level controller, EKE 347 I/O configuration MASTER AKVA (ICAD) 15 16 17 18 15 16 17 18 AKS 4100/ AKS 4100U When more controllers are Jumper Jumper connected via CAN bus each end 15-16 15-16 of the bus must be terminated with a jumper between 15 and 16.
  • Page 15 User Guide | Liquid level controller, EKE 347 Example 2 Termination Termination Example 3 Termination Termination Alarm on the external display - MMIGRS2 ERR31 If the communication to the display is not carried out correctly, it will send an “ERR31” error notification.
  • Page 16 User Guide | Liquid level controller, EKE 347 Modbus parameters Software version: 1.62.xx Label Parameter name Default Unit Deci- Modbus Locked EEPROM Enumeration value value mals by main switch Main switch 3001 0 = Off | 1 = On Liquid level setpoint...
  • Page 17 User Guide | Liquid level controller, EKE 347 Valve B capacity 3047 Valve C capacity 3048 ICAD takeover OD 3052 IO module setup 3091 0 = Not used | 1 = Used CAN ID 4032 Can baudrate 4033 0 = 20k | 1 = 50k | 2 = 125k | 3 = 250k | 4...
  • Page 18 User Guide | Liquid level controller, EKE 347 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.