Do you have a question about the EKC 202D and is the answer not in the manual?
Questions and answers
Leopold Makambila
January 16, 2025
Is there a possibility with the EKC 202D2 to correct the temperature sensor reading offset,
1 comments:
Mr. Anderson
February 3, 2025
Yes, the Danfoss EKC 202D can correct the temperature sensor reading offset. This is done using the parameters r09 and r10, which allow for the correction of the signal from sensors S4 and S3, respectively. Both parameters have a correction range of -10.0 K to 10.0 K.
Page 12
If the function is controlled by a signal at the DI1 or DI2 input, the relevant status can be seen here in the menu. Selection of application --- Appl. Mode (only output in Danfoss The controller can be defined in various ways. Here you set which of the 3 applica- only) tions is required.
The controller contains a number of functions that can be used to- gether with the override function in the master gateway / System Manager. Functions to be used in the gateway’s Used parameter in EKC 202D Function via data communication override function Start of defrosting Defrost control - - - Def.start...
Page 24
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
Need help?
Do you have a question about the EKC 202D and is the answer not in the manual?
Questions and answers
Is there a possibility with the EKC 202D2 to correct the temperature sensor reading offset,
Yes, the Danfoss EKC 202D can correct the temperature sensor reading offset. This is done using the parameters r09 and r10, which allow for the correction of the signal from sensors S4 and S3, respectively. Both parameters have a correction range of -10.0 K to 10.0 K.