Is there a possibility with the EKC 202D2 to correct the temperature sensor reading offset,

1 comments:
Mr. Anderson
February 3, 2025

Yes, the Danfoss EKC 202D can correct the temperature sensor reading offset. This is done using the parameters r09 and r10, which allow for the correction of the signal from sensors S4 and S3, respectively. Both parameters have a correction range of -10.0 K to 10.0 K.

This answer is automatically generated

Subscribe to Our Youtube Channel

Summary of Contents for Danfoss EKC 202D

  • Page 1 Controller for temperature control - EKC 202D Manual...
  • Page 2: Table Of Contents

    • Clock function with super cap backup Contents Introduction ....................... 2 Menu survey .....................17 Operation ......................3 Override ......................19 Applications ....................... 6 Ordering ......................19 Survey of functions ..................7 Connections .....................20 Operation ......................16 Data ........................21 Manual RS8EE202 © Danfoss 08-2010 EKC 202D...
  • Page 3: Operation

    Here the temperature reference is changed easily with a contact signal on a digital input. The signal raises the normal thermostat value by a predefined amount. At the same time the alarm limits with the same value are displaced accordingly. EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 4 An extra defrost can be activated from the control- ler’s lower-most button All the mentioned methods can be used at random – if just one of them is activated a defrost will be started. Manual RS8EE202 © Danfoss 08-2010 EKC 202D...
  • Page 5 If it is necessary to indicate the temperature on the front of refrigeration appliance, a display can be mounted. The extra dis- play will show the same information as the controller's display, but does not incorporate buttons for operation. EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 6: Applications

    The fans can be stopped during defrost and they may also follow a door switch’s open/close situation. There are several other functions for the alarm function as well as the light control, rail heat control and fans. Please refer to the respective settings. Manual RS8EE202 © Danfoss 08-2010 EKC 202D...
  • Page 7: Survey Of Functions

    When the function is changed to ON the thermostat differential will be increased by the value in r40. Activation can also take place via input DI1 or DI2 (defined in o02 or o37). EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 8 The LED on the controller’s front will show whether refrigeration is in progress. Comp Relay Here you can read the status of the compressor relay, or you can force- control the relay in the ”Manual control” mode Manual RS8EE202 © Danfoss 08-2010 EKC 202D...
  • Page 9 FanStartTemp The fan may also be started a little earlier than mentioned under “Delay of fan start after defrost”, if the defrost sensor S5 registers another allowable value than the one set here. EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 10 With setting +50°C the function is interrupted. The LED on the controller’s front will indicate whether a defrost is going on. Fan Relay Here you can read the fan relay status, or force-control the relay in “Manual control” mode. Manual RS8EE202 © Danfoss 08-2010 EKC 202D...
  • Page 11 25°C) or an NTC sensor (5000 Ohm at 25°C). NTC = 2 All the mounted sensors must be of the same type. Display step Disp. Step = 0.5 Yes: Gives steps of 0.5° No: Gives steps of 0.1° EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 12 If the function is controlled by a signal at the DI1 or DI2 input, the relevant status can be seen here in the menu. Selection of application --- Appl. Mode (only output in Danfoss The controller can be defined in various ways. Here you set which of the 3 applica- only) tions is required.
  • Page 13 * Status on relay for alarm Alarm relay * Status on relay for light Light relay *) Not all items will be shown. Only the function belonging to the selected applica- tion is shown. EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 14 (The information can be found in o65 or o66 a couple of seconds after copying has been started). Alarm destinations The importance of the individual alarms can be defined with a setting (0, 1, 2 or 3) Manual RS8EE202 © Danfoss 08-2010 EKC 202D...
  • Page 15 Semihermetic Compressors c02 min. 8 minutes and c01 min. 2 to 5 minutes ( Motor from 5 to 15 KW ) * ) Direct activating of solenoid valves does not require settings different from factory (0) EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 16: Operation

    3. Push the middle button until the parameter value is shown 4. Push the upper or the lower button and select the new value 5. Push the middle button again to freeze the value. Manual RS8EE202 © Danfoss 08-2010 EKC 202D...
  • Page 17: Menu Survey

    Used sensor type (Pt /PTC/NTC) Display step = 0.5 (normal 0.1 at Pt sensor) Max hold time after coordinated defrost 0 min 60 min Select signal for display view. S4% (100%=S4, 0%=S3) 100% 100% EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 18 If you need to return to the factory-set values, it can be done in this way: - Cut out the supply voltage to the controller - Keep both buttons depressed at the same time as you recon nect the supply voltage Manual RS8EE202 © Danfoss 08-2010 EKC 202D...
  • Page 19: Override

    The controller contains a number of functions that can be used to- gether with the override function in the master gateway / System Manager. Functions to be used in the gateway’s Used parameter in EKC 202D Function via data communication override function Start of defrosting Defrost control - - - Def.start...
  • Page 20: Connections

    Connection of display type EKA 163A. Coordinated defrost via cable connections The following controllers can be connected up in this way: EKC 204A, EKC 202D Refrigeration is resumed when all controllers have “released” the signal for defrost. Coordinated defrost via data communication Manual RS8EE202 ©...
  • Page 21: Data

    * DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be keept. ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 22 Manual RS8EE202 © Danfoss 08-2010 EKC 202D...
  • Page 23 EKC 202D Manual RS8EE202 © Danfoss 08-2010...
  • Page 24 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.