Chapter 2 - Start-Up Instructions
1204 = 0
1205 = 0
Switch OFF power, thus stopping the drive!
1701 = 11903
501 = Rated motor voltage set in Chapter 2.2.
1012 = Speed at rated motor voltage
CAUTION! Please don't forget!
11202 = SAVE MOT1 SET
Save the altered values in the non-volatile memory!

2.8 Matching the thyristor power converter unit to the system conditions concerned

- Ramp function generator
- Binary inputs and outputs
- Limit-value messages
- Additional functions
IV A
DCS 500B / DCP 500B Operating Instructions
2 - 21
3ADW000055R0401_DCS500B_Operating Instruction_e_d