Advertisement

Only if analog tacho is used as speed feedback!
Switch ON power; start drive.
12516 = increase slowly up to 20000 (=100 % speed).
Measure speed with manual tacho; balance maximum speed with R9, R48 or
R2716.
12516 = 0
Switch OFF power, thus stopping the drive!
CAUTION! Please don't forget!
11202 = SAVE MOT1 SET
Save the altered values in the non-volatile memory!
DCS 500B / DCP 500B Operating Instructions
DANGER: System components now energized!
Check motor voltage; if value has been set with 501, motor voltage must
remain constant, or must not exceed this value.
3ADW000055R0401_DCS500B_Operating Instruction_e_d
Chapter 2 - Start-Up Instructions
IV A
2 - 19