Each feed supplies half of the shelf. A&B feeds for side 1 and A&B feeds for side 2.
2.
Size each circuit to support 35 Amp List 2 Drains – 18-6AWG 2.
3.
Verify minimum loop cable length per Table 9.
4.
-48V Returns (RTN) connections must be grounded.
1.
Pull connector straight off of its header.
2.
Strip wire 1/2 inch
3.
Insert wire fully into wire entry
4.
Torque screw to 16 in-lb (1.7Nm)
5.
Repeat from 2 for all wires
6.
Push connector straight onto its header
6
7
Close the distribution door.
Repeat from Step 2 for each Converter Shelves.
2
Reference NEC Table 310-16 for applications of not more than three conductors in a raceway and correction factors for Ambient Temperatures over 30°C. Each
installation will vary and the installer should review NEC cabling requirements as well as local practice to ensure proper cable sizing is achieved for the local