CDP 31x
display
F 65
Reversal Fault
F 66
Current Difference
DCS 500B / DCP 500B Operating Instructions
Reversal of direction of current is not O.K.
The reversal of the direction of current was
not correct.
Check: - External cabling between both
thyristor power converters;
- Correct plugging in of flat cable
X18:?
Current feedback difference (deviation) be-
tween Master and Slave Drive
There is a current feedback difference (de-
viation) between Master and Slave Drive (in
twelve pulse configuration).
Check: - Parameter settings
[P 3605]
- Power-circuit cabling;
- Symmetry of control logic and
scaling of signals exchanged
between Master and Slave Drive.