ABB 500 Operating Instructions Manual page 21

Dcs 500 thyristor power converters for dc drive systems 25 to 5150 a
Hide thumbs Also See for 500:
Table of Contents

Advertisement

Only for armature-circuit power converters with SDCS-CON-2 control board &
CDP 312 panel!
Switch OFF power!
11202 = SAVE MOT1 SET
Only for controlled field supply with DCF 501B or DCF 502B !
505 = 2
503 = Rated motor field current
1305 = Field current for "Under-excitation" signal
Switch OFF power!
11202 = SAVE MOT1 SET
Before adjustment of the armature-circuit power converter is continued
(Chapters 2.4 etc.),
First perform the start-up routine for the DCF 501B or DCF 502B field supply
then: continue with Chapter 2.4
DCS 500B / DCP 500B Operating Instructions
1201 = 5
Activates the field current controller's auto-tuning function.
Action has been completed when NOT ACTIVATED is shown on the
display.
Save the altered values in the non-volatile memory!
Panel display: FEX2 OR FEX3
Scales all parameters referenced to the motor field current, such as field cur-
rent limitation or field current monitoring.
If field current is above 150A, multiply the value by 0.1 and use this number
(problem: upper limit of P503 / P504) ; the reference transferred to the DCF
500B is always 100% independent of this setting; by doing so all indications
on the panel CDP312 can be corrected quite easily by multiplying by 10
Save the altered values in the non-volatile memory!
unit (Chapter 2.9) and
3ADW000055R0401_DCS500B_Operating Instruction_e_d
Panel display: FEX2/3 AUTOTUNING
Continue with Chapter 2.4
Chapter 2 - Start-Up Instructions
IV A
2 - 9