ABB 500 Operating Instructions Manual page 19

Dcs 500 thyristor power converters for dc drive systems 25 to 5150 a
Hide thumbs Also See for 500:
Table of Contents

Advertisement

Set this only for units of the DCP 500 series!
517 = Rated power converter current
518 = 500 V (fixed!); rated power converter voltage
519 = Temperature monitoring of power section
520 = 4 ⇒ Size C4 has been selected
521 = 1 : Single bridge (2-Q) converter
507 = Rated line voltage;
CAUTION! Please don't forget!
11202 = SAVE MOT1 SET
Save the altered values in the non-volatile memory!
Resetting the warning either by:
briefly setting ("H" level) binary input X6:6
or
switching the electronics voltage supply OFF and ON again.
DCS 500B / DCP 500B Operating Instructions
Enter numerical value from rating plate here
Enter numerical value 500 V here
Enter value as indicated in the table „Technical Data" here
Coding for unit type
4 : Double bridge (4-Q) converter ⇒ on rating plate: DCP 502 xxxx
Coding for power section (bridge) type
Enter:
Rated line voltage U
= 400 V; entry for Parameter 507 ⇒ 420
Example: U
ratedline
CAUTION:
Display of the line voltage feedback value is 5 % too high!
Switching thresholds referenced to the line voltage, how-
ever, are correct!
3ADW000055R0401_DCS500B_Operating Instruction_e_d
Chapter 2 - Start-Up Instructions
⇒ on rating plate: DCP 501 xxxx
in V * 1.05
ratedline
IV A
2 - 7