Internal Alarms/Warnings
Displayed Alarm
E-Code
Engine Ignition
4502
Coil #1
Engine Ignition
4503
Coil #1
Engine Ignition
4504
Coil #1
Engine Ignition
4507
Coil #1
Engine Ignition
4602
Coil #2
Engine Ignition
4603
Coil #2
Engine Ignition
4604
Coil #2
Engine Ignition
4607
Coil #2
Engine Ignition
4702
Coil #3
Engine Ignition
4703
Coil #3
Engine Ignition
4704
Coil #3
Engine Ignition
4707
Coil #3
Engine Ignition
4802
Coil #4
Engine Ignition
4803
Coil #4
Engine Ignition
4804
Coil #4
Engine Ignition
4807
Coil #4
Engine Fuel Valve
4900
1 Position
Engine Fuel Valve
4901
1 Position
Engine Fuel Valve
4902
1 Position
Engine Fuel Valve
4903
1 Position
Engine Fuel Valve
4904
1 Position
Engine Fuel Valve
4907
1 Position
Engine Fuel Valve
4915
1 Position
38
Alarm/
Warning
Ignition Coil 1 Fault — Data erratic, intermittent, or incorrect.
A
Ignition Coil 1 Fault — Voltage above normal range; shorted to high
A
source.
Ignition Coil 1 Fault — Voltage below normal range; shorted to low
A
source; open circuit.
Ignition Coil 1 Fault — Mechanical system not responding correctly.
A
Ignition Coil 2 Fault — Data erratic, intermittent, or incorrect.
A
Ignition Coil 2 Fault — Voltage above normal range; shorted to high
A
source.
Ignition Coil 2 Fault — Voltage below normal range; shorted to low
A
source; open circuit.
Ignition Coil 2 Fault — Mechanical system not responding correctly.
A
Ignition Coil 3 Fault — Data erratic, intermittent, or incorrect.
A
Ignition Coil 3 Fault — Voltage above normal range; shorted to high
A
source.
Ignition Coil 3 Fault — Voltage below normal range; shorted to low
A
source; open circuit.
Ignition Coil 3 Fault — Mechanical system not responding correctly.
A
Ignition Coil 4 Fault — Data erratic, intermittent, or incorrect.
A
Ignition Coil 4 Fault — Voltage above normal range; shorted to high
A
source.
Ignition Coil 4 Fault — Voltage below normal range; shorted to low
A
source; open circuit.
Ignition Coil 4 Fault — Mechanical system not responding correctly.
A
Fuel Mixer — Data valid but above normal operating range; high severe
A
level.
Fuel Mixer — Data valid but below normal operating range; high severe
A
level.
Fuel Mixer — Data erratic, intermittent, or incorrect.
A
Fuel Mixer — Voltage above normal range; shorted to high source.
A
Fuel Mixer — Voltage below normal range; shorted to low source; open
A
circuit.
Fuel Mixer — Mechanical system not responding correctly.
A
Fuel Mixer — Data valid but above normal operating range; least severe
W
level.
Description
Power Zone 410
®
Controller Owner's Manual
Need help?
Do you have a question about the Power Zone 410 and is the answer not in the manual?
Questions and answers