Using the CX-Process Monitor

3-2

Using the CX-Process Monitor

3-2-1 Setting and Compiling Monitor Tags for CX-Process Monitor

1, 2, 3...
AI
4-point
Terminal
(AD041)
AO
4-point
Terminal
(DA041)
132
To transfer tag data to the CX-Process Monitor, take the following three steps.
1. Register the function block for data exchange.
Note The following function blocks can be used to exchange data:
Blocks Send Terminal to Computer (block models 401 to 404), AO/
DO terminal to All Nodes (block models 407 or 408), and AO/DO Ter-
minal Settings from Computer (block models 409 or 410).
2. Set the tag names.
3. Compile the monitor tags.
Registering Function Blocks for Data Exchange with CX-Process Monitor
To monitor function blocks, contact signals, or analog signals (including parame-
ters) from the CX-Process Monitor, register a Block Send Terminal to Computer
(block model 401, 402, 403 or 404) or AO/DO Terminal to All Nodes (block model
407 or 408) Function Block, and designate the desired data in the function block
as the source.
To set contact signals or analog signals (including the parameter) from the CX-
Process Monitor, register a AO/DO Terminal Settings from Computer (block
model 409 or 410) Function Block.
Example
1-Block Send
Send
Terminal to Computer
designation
Basic PID
Send
desig-
nation
Square
Basic PID
Root
Example: A 1-Block Send Terminal to Computer is registered and block ad-
dress 001 is designated as a source.
CPU Unit I/O Memory
DM Area
Execute
1-Block Send
Execute
Terminal to Computer
Designated as source
Section
3-2
Data
Memory
Area for
Node
Terminal,
Area to
send to
computer