MECHATROLINK Settings
6-2-3

MECHATROLINK Communications Settings

PCU's
address
Bits 08 to 15
1856 hex
Transfer cycle
1857 hex
00 (fixed)
Transfer Cycle
In addition to the scan list, the following four PCU settings are also for
MECHATROLINK communications.
• Transfer cycle
• Communications cycle
• Number of communications retries
• C2 master connection
Of these settings, the transfer cycle and communications cycle must always
be set when using the PCU. The settings for MECHATROLINK communica-
tions are set as the PCU's Common Parameters.
Set the two words of data in the PCU's internal addresses 1856 hex and
1857 hex as shown in the following table. The Common Parameters settings
saved in the PCU's internal flash memory are enabled when the PCU power is
turned ON or the Unit is restarted.
Contents
Bits 00 to 07
Communications
cycle
07 to 04
03 to 00 C2 master connection:
C2 mas-
Number
ter con-
of com-
nection
munica-
tions
retries
The transfer cycle is the cycle used for sending and receiving data with
MECHATROLINK communications. Data (sent and received) is constantly
exchanged along the MECHATROLINK communications path during every
transfer cycle. The set value and setting range for the transfer cycle depends
on the type and number of MECHATROLINK devices connected. When a W-
series Servo Drive equipped with a JUSP-NS115 MECHATROLINK-II Appli-
cation Module or with built-in MECHATROLINK-II communications is con-
nected to the PCU, the setting range for the transfer cycle is 0.5 to 4 ms.
When a G-series Servo Drive is connected to the PCU, the setting range for
the transfer cycle is 1 to 4 ms.
Transfer cycle:
00 hex: 1 ms (default setting)
01 hex: 1 ms
02 hex: 2 ms
03 hex: 3 ms
04 hex: 4 ms
A2 hex: 0.25 ms
Communications cycle:
Sets a multiplier to obtain integer multiples of the transfer
cycle.
Set value: 00 to 20 hex
The default setting 00 is the same as when the cycle is set to
3.
Set as follows:
G Series
Transfer cycle × communications cycle (multiplier) ≤ 16 ms.
Other Series
Transfer cycle × communications cycle (multiplier) ≤ 32 ms
The transfer cycle must be between 1 and 4 ms.
0: No C2 master (default setting)
1: C2 master connected
Number of communications retries:
Set value: 0 to 7, F
The default setting 0 is the same as when the number of retries
is set to 1.
When F is specified, the number of retries is 0 (no retries).
Section 6-2
Setting
05 hex: 5 ms
06 hex: 6 ms
07 hex: 7 ms
08 hex: 8 ms
A5 hex: 0.5 ms
227