Setup and usage

2
Setup and usage
2.1

MECHATROLINK-II I/O mapping

2.1.1

Unit numbers

The GRT1-ML2 must have a MECHATROLINK-II address to be identified on
the MECHATROLINK-II network. With this address, the TJ1-MC__
connected to the TJ1-ML__ can exchange I/O data with the GRT1-ML2.
2.1.2

SmartSlice I/O mapping

The I/O data of the SmartSlice I/O Units is transferred to the TJ1-MC__
controller. Then the data is automatically mapped in the I/O memory of the
TJ1-MC__. The mapping is determined by:
The type of the SmartSlice I/O Unit
The order of the SmartSlice I/O Units
The I/O data from GRT1-ML2 units is mapped in the TJ1-MC__ in order of
the GRT1-ML2 addresses. For example, the I/O data of a GRT1-ML2 unit
with address 67 hex is mapped before the I/O data of a GRT1-ML2 unit with
address 68 hex.
The TJ1-MC__ allocates digital I/O points in blocks of 32 points.
The GRT1-ML2 does not support the on-line configuration of
SmartSlice I/O Units. However, other communications units can
change the parameters of a SmartSlice I/O Unit and store this con-
figuration in the SmartSlice I/O Unit.
Use of a SmartSlice I/O Unit with a non-default configuration can
lead to SmartSlice I/O allocation errors.
GRT1-ML2 MANUAL
The automatic I/O mapping of SmartSlice I/O Units in the exam-
ples given below assumes that each SmartSlice I/O Unit has the
default I/O memory settings.
I/O mapping example 1
67 hex
#1
#2
GRT1-ML2
ID4
AD2
ID4
In
In
In
In
32
40
48
56
33
41
49
57
34
42
50
58
35
43
51
59
36
44
52
60
37
45
53
61
38
46
54
62
39
47
55
63
Analog Inputs
0
1
With a MECHATROLINK-II network as shown in the figure, the response of
the system when the network is initialized
GRT1-ML2: 67(32/8/6/0/2/0/2)
where:
67 is the GRT1-ML2 address (hexadecimal)
32 is the start address of the digital I/O
1. To initialize the network, execute the command
MECHATROLINK(unit,0), reset the system, or turn the power on.
#3
#4
#5
#6
DA2
OD4
ROS2
Out
Out
32
40
33
41
34
42
35
43
36
44
37
45
38
46
39
47
Analog Ouputs
0
1
1
is:
Out
Out
48
56
49
57
50
58
51
59
52
60
53
61
54
62
55
63
11