Altronix Trove Mercury kits are pre-assembled and consist of Trove1M1 enclosure/backplane with factory installed Altronix power supply/charger
and sub-assemblies. These kits also accommodate various combinations of Mercury boards for up to four (4) doors in a single enclosure.
120VAC
60Hz
Altronix
Input
Model
Current
Number
(A)
T1MK1F4
–
3.5
T1MK1F4Q
3.5
P
T1MK1F4D
–
3.5
T1MK1F4DQ
3.5
P
T1MK1F4S
–
3.5
T1MK1F4SQ
3.5
P
T1MK1F4SD
–
3.5
T1MK1F4SDQ
3.5
P
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top two (2) keyholes in the enclosure. Install two upper fasteners and screws
in the wall with the screw heads protruding. Place the enclosure's upper keyholes over the two upper screws; level and secure.
Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the
enclosure's upper keyholes over the three upper screws. Install the two lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model T112 or equivalent) in desired location, opposite hinge.
Slide the tamper switch bracket onto the edge of the enclosure approximately 2" from the right side (Fig. 1, pg. 2).
Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Position Mercury access controller modules over corresponding spacers and depress onto
snap on spacers, Fig. 2-5, pg. 3-6.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow4NB,
and corresponding Sub-Assembly Installation Guide for LINQ2, ACM4(CB), PDS8(CB)
and VR6 for further installation instructions.
6. Mount backplane to enclosure with hardware.
Hardware:
Snap On Spacer
- 2 -
Configuration Chart:
Nominal DC
Output Voltage
[DC]
Power
Power
Supply
Supply
Board
Board
24VDC
Input
Battery
Output
Fuse
Fuse
Range
Rating
Rating
(V)
5A/
7.5A/
20.28-
250V
32V
26.4
5A/
7.5A/
20.28-
250V
32V
26.4
5A/
7.5A/
20.28-
250V
32V
26.4
5A/
7.5A/
20.28-
250V
32V
26.4
5A/
7.5A/
20.28-
250V
32V
26.4
5A/
7.5A/
20.28-
250V
32V
26.4
5A/
7.5A/
20.28-
250V
32V
26.4
5A/
7.5A/
20.28-
250V
32V
26.4
Installation Instructions:
|
5/16" Pan Head Screw |
Overview:
Maximum Supply
[Aux]
Current
for Main and Aux.
Outputs on Power
Supply board
24VDC
and ACM4/ACM4CB
Output
Access Power
Range
Controller's
(V)
outputs (A)
20.28-
24VDC @ 3.6A
26.4
20.28-
24VDC @ 3.6A
26.4
20.28-
24VDC @ 3.6A
26.4
20.28-
24VDC @ 3.6A
26.4
20.28-
24VDC @ 3.6A
26.4
20.28-
24VDC @ 3.6A
26.4
20.28-
24VDC @ 3.6A
26.4
20.28-
24VDC @ 3.6A
26.4
Lock Nut
10A/
3A/
4
2.5
32V
32V
10A/
3A/
4
2.5
32V
32V
4
2.0
9A
2.5A
4
2.0
9A
2.5A
10A/
3A/
4
2.5
32V
32V
10A/
3A/
4
2.5
32V
32V
10A/
4
2.0
2.5A
32V
10A/
4
2.0
2.5A
32V
Edge of
Enclosure
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Trove1 Mercury Kits Installation Guide
–
–
–
–
–
–
–
–
10A/
3A/
32V
32V
10A/
3A/
32V
32V
9A
2.5A
9A
2.5A
Fig. 1
Enclosure
Need help?
Do you have a question about the TROVE T1MK1F4 and is the answer not in the manual?
Questions and answers