Altronix Trove PDK kits are pre-assembled and consist of Trove2PD2 enclosure/backplane with factory installed Altronix power supply/chargers
and sub-assemblies. These kits also accommodate various combinations of PDK red1, red2, red4 modules for up to twenty four (24) doors in
a single enclosure.
Altronix
Model Number
6.3A/
T2PDK75F16S
250V 15A/
8
5A/
T2PDK75F16SD
250V
T2PDK77F24S
6.3A/
9
250V
T2PDK77F24SD
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane(s) from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the
enclosure. Install three upper fasteners and screws in the wall with the screw heads
protruding. Place the enclosure's upper keyholes over the three upper screws,
level and secure. Mark the position of the lower three holes. Remove the enclosure.
Drill the lower holes and install the three fasteners. Place the enclosure's upper keyholes
over the three upper screws. Install the three lower screws and make sure to
tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in
desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the
enclosure approximately 2" from the right side (Fig. 1, pg. 2). Connect tamper switch
wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Mount PDK modules to TPDK2 backplane, refer to pg. 3, 4.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow104NB and
eFlow102NB and corresponding Sub-Assembly Installation Guides for
ACMS8(CB), ACMS12(CB), PDS8(CB), PD8UL(CB), VR6 for further installation instructions.
Hardware:
Nylon Spacer |
- 2 -
Configuration Chart:
Nominal DC Output Voltage
Power
Power
Supply 1
Supply 2
[DC] [Aux] [DC] [Aux]
20.17-
20.28-
9.7-
10.03-
32V
26.4
26.4
13.2
13.2
15A/
20.17-
20.28-
20.17-
20.28-
32V
26.4
26.4
26.4
26.4
Installation Instructions:
5/16" Pan Head Screw |
Overview:
Maximum Supply
Current for Main and
Aux. Outputs on Power
Supply board and
ACMS8(CB)/ACMS12(CB)
Access Power
Controller's outputs
12VDC @ 9.3A
24VDC @ 9.2A
24VDC @ 9.2A
Lock Nut
15A/
3A/
32V
32V
16
2.5
9A
2.5A
15A/
3A/
32V
32V
24
2.5
9A
2.5A
Enclosure
Edge of
Enclosure
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Trove PDK eFlow Kits Installation Guide
3.5A/
250V
–
–
2.5A
10A/
3A/
–
32V
32V
9A
2.5A
–
Fig. 1