2.7.
Timers
A unit may have up to 5 selectable timers for each system on a controller. All timers are associated with their
system, so for a % of post bleed timer looks at the bleed of that system.
2.7.a. Timer Type Selection
A pop-up screen lets you scroll through the various timer types available.
2.7.b. Timer Set Up
27.c. Pulse Timer
TIMERS - Select the type (28-Day, pulse, limit, percent,
recycle, percent of post bleed, or other event), as well
as the run times of each timer available per system.
Pulse - A water meter activated timer.
Limit - Feed with bleed with a maximum run time or
limit for one bleed cycle.
Recycle - A continuous recycle timer with ON and OFF
settings.
Percent Post Bleed - For feed after bleed for a settable
percentage of the bleed time with a maximum run time.
28-Day - A biocide or event timer.
Each timer type selected will have its own unique Set
Up submenu with additional selections specific to the
type of timer selected. The page displayed before
entering the Set Up menu of a timer provides an overall
review of the timers current settings.
ACCUMULATE - The number of gallons or liters from
water meter to count before activating timer.
RUN TIME - The amount of time for the timer to run
METER INPUT - Select water meter 1 or 2 for the
timer's activation. Water meter 1 + 2 can be selected
only if the meters have the same contact value.
BLEED INTR -
Allows the pulse timer to be interrupted
during conductivity bleed. While interrupted, you can also
define the maximum number of timer run-cycles (1-9) to
store for playback.