Tecnosystemi Apply.co pico basic 30 User Manual page 68

Wall-mounted heat recovery ventilation unit
Table of Contents

Advertisement

Available languages

Available languages

FUNCTION
Removal
with humidity
threshold
Free cooling
Free heating
68
DESCRIPTION
The system monitors the humidity in the environment.
When the ambient air exceeds the humidity threshold, the device is enabled as a REMOVAL-only
function until the humidity returns to the required value.
To detect humidity of the internal room, REMOVAL ventilation is enabled at minimum speed.
Upon exceeding the humidity threshold, the recovery device switches to REMOVAL mode at
maximum speed.
Upon reset of the humidity value, the device resumes the REMOVAL mode at minimum speed.
The factory set moisture value is 50%.
To change the desired humidity threshold (40%, 50% or 60%) to enable the function, use the
speed keys:
MINIMUM speed / 1 LED blink/Set level 40%;
MEDIUM speed / 2 LED blinks/ Set level 50%;
MAXIMUM speed / 3 LED blinks/ Set level 60%.
Upon completion of this operation, the white LED remains fixed to confirm that the selected
humidity value has been correctly set.
Available on PICO PRO+ models only
Upon activating the FREE COOLING function, the device starts an indoor and outdoor
temperature verification cycle.
The device is first enabled in REMOVAL mode to measure the indoor ambient temperature,
then in INTRODUCTION mode to detect the outdoor temperature.
The verification duration varies depending on the environmental conditions, but it does not
exceed 10 minutes.
After the verification, should the device detect a difference between the outdoor temperature
and the indoor temperature greater than 3 °C, it automatically enables the FREE COOLING
mode.
FREE COOLING mode remains active for 60 min. with INTRODUCTION ventilation at MAXIMUM
speed. At the end of the 60 min, a new verification is enabled.
In this mode, should the FREE COOLING conditions not be met, the shutter closes, the device
moves to stand by for 60 min and the LED blinks.
Available on PICO PRO+ models only
Upon activating the FREE COOLING function, the device starts an indoor and outdoor
temperature verification cycle.
The device is first enabled in REMOVAL mode to measure the indoor ambient temperature,
then in INTRODUCTION mode to detect the outdoor temperature.
The verification duration varies depending on the environmental conditions, but it does not
exceed 10 minutes.
After the verification, should the device detect a difference between the outdoor temperature and
the indoor temperature greater than 3 °C, it automatically enables the FREE HEATING mode.
FREE HEATING mode remains active for 60 min. with INTRODUCTION ventilation at MAXIMUM
speed. At the end of the 60 min, a new verification is enabled.
In this mode, should the FREE HEATING conditions not be met, the shutter closes, the device
moves to stand by for 60 min and the LED blinks.