Delete Rf Device; Rf Zone Properties; Gross Attack; Minor Attack - Bosch Solution 6000-IP Installation Manual

Hide thumbs Also See for Solution 6000-IP:
Table of Contents

Advertisement

Solution 6000-IP
Installation Manual
Inputs > RF Zone >

Delete RF Device

This menu allows you to delete an RF device.
1) Press [MENU] + [3] + [3] + [1] and use the up and
down arrows to highlight the zone in the list and
press [OK]. The keypad will only list zones that have
an ID programmed. If no zones have an ID number
programmed, the keypad will display:
No Matching List Items
Found!
Press  OK or MENU
Delete Device ID Zn1
Zone 1 Name
007407097
Press OK or MENU
2) Press [OK] to DELETE the RF device and exit or press
[MENU] to exit without deleting.
Inputs > RF Zone >
Test RF Device
This menu allows you to test just how good the current
position is for an RF device. Enter the command and you
will be presented with a list of RF zones in the current area
that are available for test. Use the arrow keys to highlight
the zone to test and press OK. At any time press menu to
exit.
1) Press [MENU] + [3] + [3] + [2] and use the up and
down arrows to highlight the zone you want to test
in the list and press [OK]. Alternatively, you can
enter the zone number directly and press [OK]. The
system will only list RF zones in the current area.
Zn2 Zone 2 Name
W a i t i n g for Trigger!
Press OK or MENU
2) Once a signal is received the following information
will be displayed.
Zn2 Zone 2 Name
Transmissions = 001
Signal = Good
Press OK or MENU
Signal can = Good, Average or Relocate
Every time you send a transmission, the number of
transmissions will increment and the average of the signals
with be displayed. Be sure to send a few transmissions to
establish a more accurate signal measurement.
7-12
Input Programming
MENU 3-3-1
MENU 3-3-2
Inputs > RF Zone > RF Zone Properties

RF Zone Properties

The following sub-menus allow you to configure Digiflex
RF sensors.
Inputs > RF Zone > RF Zone Properties

Gross Attack

This menu allows you to set the sensitivity of internal and/
or external shock sensors connected to the Digiflex RF
sensors.
1) Enter [MENU] + [3] + [3] + [3] + [0]. The keypad will
display the current gross attack setting.
Gross Attack Zn1
070
Press 0-9 OK to SAVE
2) Using the numeric keys, enter the new setting.
Valid entries are 001 – 100 / 000 to disable.
3) Press [OK] to save and exit or press [MENU] to exit
without saving.
Inputs > RF Zone > RF Zone Properties

Minor Attack

This menu allows you to set the sensitivity of internal and/
or external shock sensors connected to the Digiflex RF
sensors.
1) Enter [MENU] + [3] + [3] + [3] + [1]. The keypad will
display the current minor attack setting.
Minor Attack Zn1
006
Press 0-9 OK to SAVE
2) Using the numeric keys, enter the new setting.
Valid entries are 001 – 100 / 000 to disable.
3) Press [OK] to save and exit or press [MENU] to exit
without saving.
MENU 3-3-3
MENU 3-3-3-0
0
MENU 3-3-3-1
0
Bosch Security Systems 10/22 BLCC615I
7
0
0
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cc615gwfCc615pb

Table of Contents