To Install The Discharge Grille; Opening And Closing The Unit; To Open The Outdoor Unit; To Close The Outdoor Unit - Daikin EBLA16D V3 Installation Manual

Hide thumbs Also See for EBLA16D V3:
Table of Contents

Advertisement

F
Drain holes
Snow
In regions with snowfall, snow might build up and freeze between the
heat exchanger and the casing of the unit. This might decrease the
operating efficiency. To prevent this:
1 Remove the knockout hole (a) by tapping on the attachment
points with a flat head screwdriver and a hammer.
a
2 Remove the burrs, and paint the edges and areas around the
edges using repair paint to prevent rusting.
NOTICE
When making knockout holes, do NOT damage the casing
and underlying piping.
4.2.4

To install the discharge grille

1 Insert the hooks. To prevent breaking the hooks:
▪ First insert the bottom hooks (2×).
▪ Then insert the top hooks (2×).
2 Insert and fix the screws (4×)(delivered as accessory).
1
2
4 N • m
T25
4.3

Opening and closing the unit

4.3.1

To open the outdoor unit

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620239-1B – 2022.05
4.3.2
2
1
5
5.1
▪ Water pressure. The maximum water pressure is 4 bar. Provide
▪ Water temperature. All installed piping and piping accessories
2
1
1

To close the outdoor unit

NOTICE
Speed nut. Make sure the speed nut for the top screw is
correctly attached to the service cover.
3.55 N • m
2
2
a
Speed nut

Piping installation

Preparing water piping

NOTICE
In case of plastic pipes, make sure they are fully oxygen
diffusion tight according to DIN  4726. The diffusion of
oxygen into the piping can lead to excessive corrosion.
NOTICE
Water circuit requirements. Make sure to comply with the
water pressure and water temperature requirements
below. For additional water circuit requirements, see the
installer reference guide.
adequate safeguards in the water circuit to ensure that the
maximum pressure is NOT exceeded.
(valve,
connections,...)
MUST
temperatures:
5 Piping installation
1
a
2
withstand
the
following
Installation manual
17

Advertisement

Table of Contents
loading

Table of Contents