SVS connection requirements
Wire size
Only use harmonised wire providing double
insulation and suitable for 220~240 V
2-core cable
Minimum cable section of  0.75 mm²
Polarity of terminal 1
Polarity of terminal 2
It is mandatory to use a surge killer to protect the internal circuit of
the outdoor unit PCB (e.g. a separate surge killer diode or a relay
with a built-in surge killer diode).
Example:
+
b
X2M
24 V DC
1
2
a
+
d
c
a
SVS output terminal
b
DC power supply
c
Relay
d
Surge killer diode
e
AC power supply
f
External alarm
SVEO output
The SVEO output is a contact on terminal X1M that closes in case of
occurrence of general errors. See
Overview"  [ 4   39] for errors that will trigger
and
"20.1.1  Error codes:
this output.
SVEO connection requirements
Voltage
Maximum current
Wire size
Only use harmonised wire providing double
insulation and suitable for the applicable
voltage
2-core cable
Minimum cable section of  0.75 mm²
For the SVEO connection it is recommended to use a shielded
cable. The cable shield must be earthed at the marked earthing point
that is located on the support frame of the terminal.
V1
X1M
1 2
a
b
c
a
Earthing point
b
Cable shield
c
Cable to SVEO output device
INFORMATION
Sound data about the refrigerant leakage alarm are
available in the technical data sheet of the user interface.
E.g. the BRC1H52* controller generates an alarm of 65 dB
(sound pressure, measured at 1  m distance from the
alarm).
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600329-1E – 2023.02
+
240 V AC
e
f
Overview" [ 4  14]
"8.1 Error codes:
220~240 V AC
0.5 A
Y1
X1M
1 2
a
b
c
16 Electrical installation
16.5
To connect the cool/heat selector
switch option
In order to control the cooling or heating operation from a central
location,
the
following
optional
(KRC19-26A) can be connected:
1 Remove the mounting screw from the terminal mounting plate.
V1
2 Turn the terminal mounting plate to reach the other side of the
plate.
V1
3 Connect the cool/heat selector switch to terminal X3M.
V1
1
A
X3M
KRC19-26A
2
B
3
C
X3M
Terminal on the unit
KRC19-26A
Cool/heat selector switch
4 Turn back the terminal mounting plate and reinstall the screw.
5 Fix the cables with cable ties.
V1
a
b
a
Cool/heat selector switch cable
b
Cable tie
6 Turn ON the DIP switch (DS1‑1). See
components" [ 4  35] for more information on the DIP switch.
cool/heat
selector
switch
Y1
Y1
Y1
Y1
a
b
"18.1.3  Field setting