Rotate housing

To improve field access to wiring or to better view the optional
display:
Procedure
1. Loosen the housing rotation set screw using a 5/64-inch hex
wrench.
2. Turn the housing left or right up to a maximum of 180° from
its original position.
3. Re-tighten the housing rotation set screw to a maximum of 7
in-lb when desired location is reached.
NOTICE
Over-rotating will damage the transmitter.
Figure 3-1: Housing rotation
Rosemount 3051C original position aligns with "
(1)
original position is the opposite side of the bracket holes.
Quick Start Guide
(1)
A. Housing rotation set screw (5/64-inch)
A
" side; Rosemount 3051T