Specific Conditions for Safe Use:
1. If the apparatus is fitted with an optional 90 V transient
suppressor, it is not capable of withstanding the 500 V
insulation test required by clause 6.3.12 of IEC 60079-11. This
must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a
protective polyurethane paint finish; however, care must be
taken to protect it from impact or abrasion if located in Zone 0.
9.7.4  N7 IECEx Type n
Certificate
Standards
Markings
Specific Condition for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V
insulation test required by clause 6.5.1 of IEC 60079-15. This
must be taken into account when installing the apparatus.
9.8 
Brazil
9.8.1  E2 Brazil Flame-proof
Certificate
Standards
Markings
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm with less than 1
mm thickness that forms a boundary between zone 0 (process
connection) and zone 1 (all other parts of the equipment).
The model code and datasheet are to be consulted for details
of the diaphragm material. Installation, maintenance, and
use shall take into account the environmental conditions to
which the diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be followed
in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended to be repaired.
40
IECEx BAS 09.0077X
IEC60079-0: 2017, IEC60079-15: 2010
Ex nA IIC T5 Gc (-40 °C ≤ T
UL-BR 13.0643X
ABNT NBR IEC 60079-0: 2013; ABNT NBR IEC 60079-1:
2016; ABNT NBR IEC 60079-26: 2016
Ex db IIC T6...T4 Ga/Gb
T6: –60 °C ≤ T
≤ +70 °C
a
T4/T5: –60 °C ≤ T
≤ +70 °C)
a
≤ +80 °C
a
February 2024
Emerson.com/Rosemount