Quick Start Guide
4 

Set the switches

Set Alarm and Security switch configuration before installation, as
shown in
Figure 4-1: Electronics board
Without LCD display
A. Alarm
B. Security
The Alarm switch sets the analog output alarm to high or low.
Default Alarm is high.
The Security switch allows (
configuration of the transmitter.
Default Security is off (
To change the switch configuration:
Procedure
1. If the transmitter is installed, secure the loop, and remove
power.
2. Remove the housing cover opposite the field terminal side.
Do not remove the instrument cover in explosive atmospheres
when the circuit is live.
3. Slide the Security and Alarm switches into the preferred
position using a small screwdriver.
14
Figure
4-1.
 WARNING
With LCD display
) or prevents (
).
February 2024
) any
Emerson.com/Rosemount