Enter the device number to be
isolated (in the example it is device
number 028). Press the YES key. The
display will change to show, figure 47.
Scroll down until "Status ", is
between the > and < characters, as
shown in figure 48.
Press the YES key until the
display changes to show, figure 49.
Scroll down until "Transmit
Event ", is between the > and <
characters, as shown in figure 50.
Press the YES key. The device on the Networked Panel will now be isolated. Press the NO key until the display shows Panel
In Access. Return the Panel Controls keyswitch to the OFF position, this will now show that the system is clear. The
Networked Panel will indicate that a Device has been isolated by sounding a soft bleep at approximately 20 second intervals
and the "ISOLATED" lamp will illuminate.
12.0

Re-instating an Isolated Network Device.

Turn the Panel Controls,
keyswitch to the ON position, this will
result in the display changing to show
figure 51.
Press the 0 key. The display will.
change to show, figure 52
Panel Type : PAN
> Panel
:
Device
:
YES= Select
Figure 47
Device
: 028
> Status
: ACTIVE
Transmit Event
YES = Select
Figure 48
Device
: 028
> Status
: ISOLATE
Transmit Event
YES = Select
Figure 49
Status
: ISOLATE
>
Transmit Event
^^^^^^^^^^^^^^^^^^^^
YES = Select
Figure 50
Panel In Access
Date
Figure 51
***
Options
>
Passwords
Time and Date
YES= Select
Figure 52
13
System 5000
04
<
028
Time
<
Time
<
Time
<
Time
Time
***
<
Time

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire system 5096

Table of Contents