Isolating A Device Prior To An Alarm Event - EMS FIRE SYSTEM 5000 User Manual

Hide thumbs Also See for FIRE SYSTEM 5000:
Table of Contents

Advertisement

E.M.S Group
Scroll down until "Status is", is
between the > and < characters, as
shown in figure 18.
Press the YES key. The display will
change to show, figure 19.
The device will now be isolated. Press the NO key until the display shows Panel In Access. Return the Panel Controls
keyswitch to the OFF position, this will now show that the system is clear. The panel will indicate that a Device has been
isolated by sounding a soft bleep at approximately 20 second intervals. The "ISOLATED" lamp will illuminate on the
Control Panel.

9.0 Isolating A Device Prior To An Alarm Event

It is possible when work is to be carried out on a device to isolate the unit beforehand, to ensure an alarm condition does not
occur. To isolate a device prior to an alarm activation carry out the following sequence of operations.
Turn the Panel Controls keyswitch to
the ON position, this will result in the
display changing to show, figure 20.
Press the 0 key. The display will
change to show, figure 21.
Scroll down using the ! key until
"Fire System Opts'' is shown between
the > and < characters. The display
will show, figure 22.
Number is : 005
> Status is : ACTIVE
Zone is
YES = Select
Figure 18
Number is : 005
> Status is :ISOLATE
Zone is
YES = Select
Figure 19
Panel In Access
Date
Figure 20
***
Options
> Passwords
Time and Date
YES = Select
Figure 21
Logging
>
Fire System Opts
Remote Access
YES = Select
Figure 22
8
System 5000
<
: 01
Time
<
: 01
Time
Time
****
<
Time
<
Time