E.M.S Group
Enter the device number to be re-
instated (in the example it is device
number 005). Press the YES key. The
display will change to show, figure 35.
Scroll down until "Status is", is
between the > and < characters, as
shown in figure 36.
Press YES. The display will change to
show, figure 37.
Press YES. The Display will change to
show, figure 38.
The device will now be reinstated. Press the NO key until the display shows Panel In Access. Return the Panel Controls
keyswitch to the OFF position, this will now show that the system is clear. If this was the only device isolated on the system the
"ISOLATED" lamp will extinguish. If further devices are isolated the panel will sound a soft bleep at approximately 20 second
intervals and the "ISOLATED" lamp will be illuminated on the Control Panel.
11.0

Isolating a Network Device.

If a device on a Networked Panel develops a fault, and engineering support is not immediately available, it is possible to isolate
the device by carrying out the following sequence of operations on the Control Panel.
When trying to reset an alarm
condition if the device is still in alarm,
pressing the RESET/LED TEST button
will result in the display changing to
show, figure 39.(example )
**Device Status **
> Number is : 005
Status is : ISOLATE
YES = Select
Figure 35
Number is : 005
>
Status is :ISOLATE
Zone is
YES = Select
Figure 36
Number is : 005
>
Status is :TEST
Zone is
YES = Select
Figure 37
Number is : 005
>
Status is :ACTIVE
Zone is
YES = Select
Figure 38
Device NOT CLEAR :
RADIO CALLPOINT
Push Any Key
Figure 39
11
System 5000
<
Time
<
: 01
Time
<
: 01
Time
<
: 01
Time