E.M.S Group
TAMPER
This display shows a tamper alarm has been activated from the device shown on the controllers display. The following alarm
screen will be shown;
Indicates the alarm
type and number.
Indicates device & →
zone allocation
number.
FAULT
This display shows a fault has been activated from the device shown on the controller. To determine which type of fault has
occurred, the systems log must be interrogated. The following fault screen will be shown;
Indicates the alarm
type and number.
Indicates device & →
zone allocation
number.
FAULT: BT MN
On a system mains failure the controller will switch into battery safe mode. This will turn the display completely off and the
Supply Healthy LED will extinguish. Pressing any key on the panel will re-activate the display and the following fault screen
will be shown;
Indicates the alarm
type and number.
Fault Description
01 TAMPER
RADIO CALL POINT
ZONE 01
TAMPER represents a devices tamper circuit has been activated.
Device Fault LED will also light and the controllers buzzer will
sound, when the above screen is displayed.
01 FAULT
RADIO CALL POINT
ZONE 01
FAULT covers a number of possible device faults. The systems log
must be interrogated to discover the type of fault received.
Associated fault types are as follows; Detector call in fail, Detector
head missing, Device low battery and Detector head requires
changing due to contamination.
Device Fault LED will also light and the controllers buzzer will
sound, when the above screen is displayed.
01 FAULT
CONTROL PANEL
FAULT:BT MN
FAULT BT represents the units batteries are no longer being
charged.
FAULT MN represents the controller has had a mains failure.
The Common Fault LED will also light when the above screen is
displayed.
Indicates the total
number of system
← alarms.
TOT 01
← Shows default or
programmed
DEVICE 005
device text.
Indicates the total
number of system
← alarms.
TOT 01
← Shows default or
programmed
DEVICE 005
device text.
← faults.
TOT 01
← Shows where
TIME
19
System 5000
Indicates the total
number of system
the fault is located
.

Advertisement