Press YES. The display will change to
show, figure 23.
Press YES. The display will change to
show, figure 24.
Press the 0 key. The display will
change to show, figure 25.
Enter the device number to be isolated
(in the example it is device number
005). Press the YES key. The display
will change to show, figure 26.
Scroll down until "Status is", is
between the > and < characters, as
shown in figure 27.
Press YES. The display will change to
show, figure 28.
The device will now be isolated. Press the NO key until the display shows Panel In Access. Return the Panel Controls
keyswitch to the OFF position, this will now show that the system is clear. The panel will indicate that a Device has been
isolated by sounding a soft bleep at approximately 20 second intervals. The "ISOLATED" lamp will illuminate on the Control
Panel.
** Fire System **
>
Dev.Isolate/Test
Net. Isolate/Test
YES = Select
Figure 23
**Device Status **
> Number is : 001
Status is : ACTIVE
YES = Select
Figure 24
Enter Device
(Numbers 1 - 256)
Number > _
YES = Finish
Figure 25
**Device Status **
>
Number is : 005
Status is : ACTIVE
YES = Select
Figure 26
Number is : 005
>
Status is : ACTIVE
Zone is
YES = Select
Figure 27
Number is : 005
>
Status is : ISOLATE <
Zone is
YES = Select
Figure 28