2.3
General Requirement for Ventilation and Maintenance
During installation ensure that the following conditions are met.
Keep at least 1000 mm of free space in front of the UPS for air flow and future
maintenance purposes.
Keep at least 300mmof free space in rear of the UPS for air-flow space.
Keep at least 300mm of free space in the top of UPS for maintenance operations.
Equipment
Front Side
Other
>1000mm
Top Side
>300mm
UPS
19
Rear Side
>300mm