Ablerex KRONOS Series Installation And Operation Manual page 22

10-40 kva ups
Table of Contents

Advertisement

 Maximum Current
Input/Output
Output Power
Voltage
10KVA/9KW
20KVA/18KW
380 V
30KVA/27KW
40KVA/36KW
10KVA/9KW
20KVA/18KW
400 V
30KVA/27KW
40KVA/36KW
10KVA/9KW
20KVA/18KW
415 V
30KVA/27KW
40KVA/36KW
(1)
The UPS is operating at rated voltage, rated power and batteries are charging but regardless of the
overload.
(2)
The UPS is operating at rated voltage and rated power but regardless of the overload.
(3)
12Vbattery blocks × 32pcs. The UPS is operating at rated voltage and rated power but regardless of
the overload.
 Recommended Size of Cables
Capacity
10KVA
20KVA
30KVA
40KVA
(1)
The recommended maximum length of cabling is less than 10meters.
(2)
Please over size neutral line N by 1.7 times of the phase line for non-linear loads.
Maximum
Input
(1)
Current
17.4 A
34.4 A
50.9 A
67.7 A
16.5 A
32.7 A
48.4 A
64.3 A
15.9 A
31.5 A
46.6 A
62.0 A
(1)
Mains Input
Output/Bypass
R/S/T/N/PE
R/S/T/N/PE
2
4 mm
2
10 mm
2
16 mm
16 mm
2
25 mm
25 mm
21
Max.
Output/Bypass
Input
(2)
Current
15.2 A
30.4 A
45.6 A
60.8 A
14.4 A
28.9 A
43.3 A
57.7 A
13.9 A
27.8 A
41.7 A
55.6 A
External Battery
(1)
Input
(2)
B+/N/B-/PE
2
4 mm
2
6 mm
2
2
Max. Battery
Discharge
(3)
Current
31 A
62 A
76 A
101 A
31 A
62 A
76 A
101 A
31 A
62 A
76 A
101 A
(1)
2
10 mm
2
16 mm
2
35 mm
2
50 mm