1.2. Storage

If the UPS is unused for an extended period of time it must be stored in a
moderate climate. The batteries should be charged for 12 hours every three
months by connecting the UPS to the utility supply and switching on the input
breaker located on the UPS rear panel. Repeat this procedure every two months if
the storage ambient temperature is above 25°C.
4
2.

Product Introduction

2.1. General Characteristics

1. True on-line technology continuously supplies your critical device with
stable, regulated, transient-free, pure-sine-wave AC power.
2.
High-efficiency PWM sine-wave topology yields excellent overall
performance.
3. The high crest factor of the inverter handles all high in-rush current
loads without the need to upgrade the power rating.
4.
User-friendly plug-and-play design allows hassle-free installation.
5.
Built-in maintenance-free, sealed batteries minimize the need for after-
sales service.
6.
To protect the unit from overloading, the UPS will automatically switch
to bypass mode in 30 seconds if loading is at 105% of rated capacity. It
will automatically switch back to inverter mode once the overload
condition ceases.
7.
Should the output become short-circuited the UPS puts the system in
stand-by mode, provides visible and audible alarms, and cuts the output
supply automatically until the short circuit situation is resolved manually.
5