Ablerex KRONOS Series Installation And Operation Manual page 42

10-40 kva ups
Table of Contents

Advertisement

Attention:
 IMMEDIATE LOAD OFF!
 For turn off the working power, switch OFF both AC Power and Batt. Power
switches in the rear of UPS.
3.4.4 Switch to bypass
(1) Push
and then click
page】.
(2) Click
to selectMode bps and then press
display
(3) The Inverter will be shut down and bypass will supply the power to the load. If the
battery is disconnected, Charger will be shut down as well.
3.4.5 Switch from normal mode to maintenance bypass
(1) Follow the processes in section 3.4.4 to switch to bypass.
(2) The Inverter will be shut down and bypass will supply the power to the load.
on LCD display, and it will take you to the 【setting
41
to excute the command on LCD