Ablerex KRONOS Series Installation And Operation Manual page 23

10-40 kva ups
Table of Contents

Advertisement

 Recommended Circuit Breaker Size
Input/Output
Voltage
380 V
400 V
415 V
(1)
The sizing takes into account 150% overload capacity
Output Power
Mains Input
10KVA/9KW
20KVA/18KW
30KVA/27KW
40KVA/36KW
10KVA/9KW
20KVA/18KW
30KVA/27KW
40KVA/36KW
10KVA/9KW
20KVA/18KW
30KVA/27KW
40KVA/36KW
22
(1)
Output/Bypass Input
20 A
40 A
63 A
80 A
20 A
40 A
63 A
80 A
20 A
40 A
63 A
80 A
(1)
20 A
40 A
50 A
80 A
16 A
32 A
50 A
80 A
16 A
32 A
50 A
80 A