VFD-L Series
Group 7: Motor Parameters
Parameters
7-00
7-01
7-02
7-03
Group 8: Special Parameters
Parameters
8-00
8-01
8-02
8-03
8-04
8-05
8-06
8-07
8-08
8-09
8-10
8-11
8-12
8-13
Functions
Motor rated current
Motor no-load current
Torque compensation
Slip compensation
Functions
DC braking voltage level 0 ~ 30%
DC braking time during
start-up
DC braking time during
stopping
Start-point for DC
braking
Momentary power loss
Max. allowable power
loss time
B.B. time for speed
search
Max. speed search
current level
Skip freq. 1 upper bound 0.0~400 Hz
Skip freq. 1 lower bound 0.0~400 Hz
Skip freq. 2 upper bound 0.0~400 Hz
Skip freq. 2 lower bound 0.0~400 Hz
Skip freq. 3 upper bound 0.0~400 Hz
Skip freq. 3 lower bound 0.0~400 Hz
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Settings
30~120 %
0 ~ 90 %
0 ~ 10
0.0 ~ 10.0
Settings
0.0 ~ 60.0 Sec
0.0 ~ 60.0 Sec
0.0 ~ 400.0 Sec
0: Stop operation after momentary
power loss.
1: Continues after momentary power
loss, speed search starts with master
freq.
2: Continues after momentary power
loss, speed search starts with min.
output freq.
0.3 ~ 5.0 Sec
0.3~5.0 Sec
30~200%
8-6
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Factory
Setting
85
50
1
0.0
Factory
Setting
0
0.0
0.0
0.0
0
2.0
0.5
150
0.0
0.0
0.0
0.0
0.0
0.0