Jog Accel Time
Settings
This parameter can be set during operation.
1 - 14
Jog Decel Time
Settings
This parameter can be set during operation.
1 - 15
Jog Frequency
Settings
This parameter can be set during operation.
The JOG function can be selected using Multi-function Input terminals (Pr.4-04 to
Pr.4-08) if programmed for Jog (d10). When the Jog terminal is "closed", the AC drive
will accelerate from Minimum Output Frequency (Pr.1-05) to Jog Frequency (Pr.1-14).
When the Jog terminal "open", the AC drive will decelerate from Jog Frequency to zero.
The accel/decel time is decided by the Jog accel/decel time (Pr.1-13). During operation,
the AC drive can not perform Jog command. And during Jog operation, other operation
commands can not be accepted, except command of RUN/STOP key on the digital
keypad.
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
F re q u e n c y
M a x .
O u t p u t
F re q .
P r. 1 - 0 0
A c c e l/D e c e l Tim e x (M a s t e r F re q . -M i n .O u tp u t F re q .)
A c tu a l A c c e l/D e c e l T im e =
d 0.1 to d 600Sec
d 0.1 to d 600Sec
d 1.0 to d 400Hz
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
T im e
M a x . O u t p u t F re q .
Factory Setting: d 10.0
Factory Setting: d 10.0
Factory Setting : d 6.0
5-7
VFD-L Series
Unit: 0.1Sec
Unit: 0.1Sec
Unit: 0.1Hz
5