Group 6: Protection Parameters
Parameters
6-00
6-01
6-02
6-03
6-04
6-05
6-06
6-07
6-08
6-09
6-10
6-11
6-12
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Functions
Over-Voltage Prevention
Level
Over-current Prevention
Level
Over-torque detection
Over-torque
detection
level
Over-torque
detection
time
Electronic thermal
overload relay
Electronic thermal
characteristic
Present fault record
Second
most
recent
fault record
Third most recent fault
record
Forth most recent fault
record
Fifth most recent fault
record
Sixth most recent fault
record
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Settings
0:disable
350~410V
0: disable
20~200%
0:disable
1:enable during constant speed
operation and continues until the
continuous limit is reached.
2:enabled during constant speed
operation and halted after detection.
3:enabled during accel and continues
before continuous output time limit is
reached.
4:enabled during accel and halted after
over-torque detection.
30 ~ 200%
0.1 ~ 10.0 Sec
0: Not used
1: Act with standard motor
2: Act with special motor
30~600 Sec
0: No fault occurred
1: oc (over current)
2: ov (over voltage)
3: oH (over heat)
4: oL (over load)
5: oL1 (electronic thermal)
6: EF (external fault)
7: Reserved
8: Reserved
9: ocA (current exceed during
acceleration)
10: ocd (current exceed during
deceleration)
11: ocn (current exceed during steady
state)
8-5
VFD-L Series
Factory
Setting
390
170
0
150
0.1
0
8
60
0