Delta VFD004L11A User Manual page 74

Compact and panel-installation drives
Table of Contents

Advertisement

Send Quote Requests to info@automatedpt.com
VFD-L Series
Fault
Name
The AC drive
temperature sensor
detects excessive heat.
The AC drive detects
that the DC bus voltage
has fallen below its
minimum value.
The AC drive detects
excessive drive output
current.
Internal electronic
overload trip
Motor overload. Check
the parameter settings
(Pr.6-03 to Pr.6-05)
Communication Error
Fault Descriptions
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Corrective Actions
1. Ensure that the ambient temperature
falls within the specified temperature
range.
2. Make sure that the ventilation holes are
not obstructed.
3. Remove any foreign objects on the
heatsinks and check for possible dirty
heat sink fins.
4. Provide enough spacing for adequate
ventilation.
Check whether the input voltage falls within
the rated AC drive's input voltage.
1. Check whether the motor is overloaded.
2. Reduce torque compensation setting as
set in Pr.7-02.
3. Increase the AC drive's output capacity.
4.
Note: The AC drive can withstand up to 150%
of the rated current for a maximum of 60
seconds.
1. Check for possible motor overload.
2. Check electronic thermal overload
setting.
3. Increase motor capacity.
4. Reduce the current level so that the
drive output current does not exceed the
value set by the Motor Rated Current
Pr.7-00.
1. Reduce the motor load.
2. Adjust the over-torque detection setting
to an appropriate setting (Pr.06-03 to
Pr.06-05).
1. Check the connection between the AC
drive and computer for loose wires.
2. Check if the communication protocol is
properly set.
7-2