VFD-L Series
Parameters & Functions table:
Value
d 0 (input not used)
M0: FWD / STOP
d 1
M1: REV / STOP
M0: RUN / STOP
d 2
M1: FWD / REV
3-Wire Operation Control mode
d 3
(M0,M1,M2)
d 4 External Fault ( Normally Open)
d 5 External Fault ( Normally Closed )
d 6 External Reset
d 7 Multi-Step Speed Command 1
d 8 Multi-Step Speed Command 2
d 9 Jog operation
d10 Accel/Decel Speed Inhibit
Explanations:
d0 Parameter Disable:
Enter value (d0) to disable any Multi-Function Input Terminal: M0, M1 (Pr.4-04), M2
(Pr.4-05) or M3 (Pr.4-06).
Note:The purpose of this function is to provide isolation for unused Multi-Function Input
Terminals. Any unused terminals should be programmed to d0 to insure they have
no effect on drive operation.
d1:Two wire operation: Restricted to Pr.4-04 and external terminals M0, M1.
d2: Two wire operation: Restrict to Pr. 4-04 and external terminals M0, M1.
Function
F W D / S T O P
M 0 " O p e n " : S to p , " C lo s e " : F W D R u n
R E V / S T O P
M 1 " O p e n " : S to p , " C lo s e " :R E V R u n
G N D
M 0 " O p e n " : S to p , " C lo s e " : R u n
R U N /S T O P
M 1 " O p e n " : F W D , " C lo s e " :R E V
R E V / F W D
G N D
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Value
First or Second Accel/Decel Time
d11
Selection
External Base Block (N.O.)
d12
(Normally Open Contact Input)
External Base Block (N.C.)
d13
(Normally Close Contact Input)
d14
Increase Master Frequency
d15
Decrease Master Frequency
d16
Run PLC Program
d17
Pause PLC Program
d18
Counter Trigger Signal
d19
Counter Reset
d20
Select ACI/deselect AVI
5-20
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Function