Dynamic Power Regulation With Several Inverters - Fronius Primo GEN24 4.0 Operating Instructions Manual

Hide thumbs Also See for Primo GEN24 4.0:
Table of Contents

Advertisement

If there is no meter in the system or if a meter has failed, the inverter limits the
feed-in power to the set value.
Example: Feed-in limitation
(without consideration of the efficiency)
PV system on Fronius inverter:
Consumption in home:
Maximum permitted feed-in power of the entire system:
Case 1: The battery can be charged
Power at grid feed-in point:
Power at inverter output:
Power into the battery:
Case 2: The battery cannot be charged
Power at grid feed-in point
Power at inverter output:
Power into the battery:
In this example, no more than 3,000 W may be fed into the grid at the grid
feed-in point. However, any loads that are located between the inverter and the
grid feed-in point can be supplied by additional power from the inverter. These
loads are also compensated as required.
Dynamic power
Example 1: Fronius SnapINverter ≤ Fronius Primo GEN24
regulation with
Only one primary meter is required for the Fronius Primo GEN24 inverter.
several inverters
The power values shown are an example. Inverter configurations with power val-
ues other than those shown in the example are possible, taking into account the
criteria for this example.
IMPORTANT!
Zero feed-in is not possible when using 2 inverters.
5,000 W
1,000 W
60 % = 3,000 W
0 W
1,000 W
3,000 W
3,000 W
4,000 W
0 W
129