13
IMPORTANT!
If necessary, an automatic circuit breaker with max. 16 A can also be used for
protection. In backup power operation, a maximum of 13 A can be provided.
The residual current circuit breaker and automatic circuit breaker must be de-
signed according to the national provisions
14
15
Strip the single conductors according
to the specifications based on the
power category of the inverter.
The cable cross-section must be selec-
ted according to the specifications for
the respective power category of the
inverter (see chapter
Permissible
cables for the electrical connection
page 67).
Connect the phase/neutral conductors
to the terminals provided. Fasten the
ground conductor at the first input to
the ground electrode terminal using a
screwdriver (TX20) and a torque of 1.8
– 2 Nm.
IMPORTANT!
The ground conductor must be con-
nected with a movement loop so that if
the cable gland fails, the ground con-
ductor is disconnected last.
Connect the stripped phase/neutral
conductors to the terminals provided.
on