Connecting the data communication cable

Modbus parti-
The inputs M0 and M1 can be selected for this purpose. A maximum of 4 Modbus
cipants
participants can be connected to the Modbus terminal on inputs M0 and M1.
IMPORTANT!
Only one primary meter, one battery and one Ohmpilot can be connected per in-
verter. Due to the high data transfer of the battery, the battery occupies 2 parti-
cipants. If the
munication"
possible to send and receive data at the same time.
Example 1:
Example 2:
"Inverter control via Modbus"
"Modbus"
Input
Battery
Input
Battery
function is activated in the
menu, no Modbus participants are possible. It is not
Fronius
Ohmpilot
Fronius
Ohmpilot
"Com-
Quantity
Quantity
Primary
Secondary
meter
meter
0
4
0
2
0
1
1
3
Quantity
Quantity
Primary
Secondary
meter
meter
1
3
0
4
0
2
0
1