Dynamic power
Example 1: Fronius SnapINverter ≤ Fronius Primo GEN24
regulation with
Only one primary meter is required for the Fronius Primo GEN24 inverter.
several inverters
The power values shown are an example. Inverter configurations with power val-
ues other than those shown in the example are possible, taking into account the
criteria for this example.
IMPORTANT!
Zero feed-in is not possible when using 2 inverters.
Settings on the user interface of the Fronius Primo GEN24 inverter:
1
2
Example 2a: Fronius SnapINverter > Fronius Primo GEN24
Two primary meters are required for the inverters.
The power values shown are an example. Inverter configurations with power val-
ues other than those shown in the example are possible, taking into account the
criteria for this example.
IMPORTANT!
With two primary meters at the feed-in point without a secondary meter, Fronius
SnapINverter and Fronius Primo GEN24 inverters cannot be displayed as a com-
bined PV system in Solar.web. Two individual PV systems must be created in Sol-
ar.web.
P
= 8,2 kW
AC nom
P
= 10 kW
AC nom
Configure the primary meter at the feed-in point in the
tion"
"Components"
menu.
Activate the limit for the entire system in the
"Export limitation"
menu. Enter the DC rated power of the entire PV system
in the
"Total DC system power"
60% or 70%) in the
"Maximum permitted feed-in power of the entire system"
input field.
6
0 0 1
7
1
"Safety and grid regulations"
input field. Enter the percentage value (50%,
"Device configura-
127