Fronius Primo 3.0-1 Installation Instructions Manual

Fronius Primo 3.0-1 Installation Instructions Manual

Hide thumbs Also See for Primo 3.0-1:
Table of Contents

Advertisement

Quick Links

Installation
Instructions
Fronius Primo - Installation
EN
Installation Instructions
42,0426,0204,EN
021-16052022

Advertisement

Table of Contents
loading

Summary of Contents for Fronius Primo 3.0-1

  • Page 1 Installation Instructions Fronius Primo - Installation Installation Instructions 42,0426,0204,EN 021-16052022...
  • Page 3: Table Of Contents

    Notes regarding dummy devices Do not earth solar modules Inverter DC connection Cable routing in the DC area Multi MPP tracker inverters - Fronius Primo 3.0 - 8.2 Data communication Routing data communication cables Installing the Datamanager in the inverter...
  • Page 4 Cleaning Serial Number Sticker for Customer Use Serial number sticker for customer use...
  • Page 5: Installation Location And Position

    Installation location and position Explanation of DANGER! safety notices Indicates immediate danger. ▶ If not avoided, death or serious injury will result. WARNING! Indicates a potentially hazardous situation. ▶ If not avoided, death or serious injury may result. CAUTION! Indicates a situation where damage or injury could occur. ▶...
  • Page 6: Proper Use

    Fronius accepts no liability for fires that can occur despite the pres- ence of the integrated arc detection/extinguishing system (e.g. fires caused by a parallel arc).
  • Page 7: Explanation Of Symbols And Choice Of Location

    Proper use also includes carefully reading and obeying all the instructions and all the safety and danger notices in the operating instructions performing all stipulated inspection and maintenance work installation as specified in the operating instructions When designing the photovoltaic system, ensure that all of its components are operated within their permitted operating ranges at all times.
  • Page 8: Installation Position

    Do not install the inverter in: Areas where ammonia, corrosive vapours, acids or salts are present (e.g. fertiliser stores, ventilation openings from cattle sheds, chemical plants, tanneries, etc.) During certain operating phases the inverter may produce a slight noise. For this reason it should not be installed close to living areas.
  • Page 9: General Comments Regarding Choice Of Location

    The inverter is suitable for installation on a sloping surface. Do not install the inverter on a sloping surface with its connection sockets at the top. Do not install the inverter at an angle on a vertical wall or column. Do not install the inverter horizontally on a vertical wall or pillar.
  • Page 10 Max. ambient temperatures: -40 °C / +55 °C Relative humidity: 0-100% The airflow within the invert- er is from the left and right to the top (cold air taken in from the left and right, hot air dissipated out of the top). The exhaust air can reach a temperature of 70 °C.
  • Page 11: Attaching The Mounting Bracket

    Attaching the Mounting Bracket Safety WARNING! Danger due to residual voltage in capacitors. This may result in an electric shock. ▶ Wait for the capacitors to discharge. The discharge time is five minutes. CAUTION! Danger due to dirt or water on the terminals and contacts of the inverter's con- nection area.
  • Page 12: Do Not Warp Or Deform The Mounting Bracket

    Do not warp or Note! When fitting the mounting bracket to the wall, ensure that the mounting deform the bracket does not become warped or deformed. mounting brack-...
  • Page 13: Fitting The Mounting Bracket To A Wall

    Fitting the mounting brack- et to a wall Tip: Install the inverter so that its display is at eye level Note! When mounting the mounting bracket on the wall, ensure that the mounting bracket does not become warped or deformed. Attaching the mounting brack-...
  • Page 14: Mounting The Inverter On A Mast

    Mounting the in- When mounting the inverter on a mast verter on a mast or a vertical carrier, Fronius recom- mends the use of a standard mast fix- ing kit. This kit enables the inverter to be mounted on round or rectangular masts with various cross-sections.
  • Page 15: Connecting The Inverter To The Public Grid (Ac Side)

    ▶ Maintenance and servicing in the power stage set of the inverter must only be carried out by Fronius-trained service technicians. CAUTION! Risk of damage to the inverter as the result of incorrectly tightened terminals. Incorrectly tightened terminals can cause heat damage to the inverter that may result in a fire.
  • Page 16: Ac Terminals

    AC terminals Ground conductor / earthing Phase conductor Neutral conductor Max. cross-section of each conductor cable: 16 mm² Min. cross-section of each conductor cable: in accordance with the fuse rating on the AC side, but at least 2.5 mm² The AC cables can be connected to the AC terminals without ferrules.
  • Page 17: Requirements For The Neutral Conductor

    IMPORTANT!Repeat the procedure if the cable has been disconnected and is to be re-connected. Requirements Note! for the neutral Ensure that the grid neutral conductor is grounded. This may not be the case conductor for IT grids (insulated grids with no grounding); it will then not be possible to use the inverter.
  • Page 18: Maximum Fuse Rating On Alternating Current Side

    IMPORTANT! The PE ground conductor of the AC cable must be laid in such a way that it is the last to be disconnected in the event that the strain-relief device should fail. This can be ensured, for example, by making it somewhat longer and by laying it in a loop.
  • Page 19 For this situation, a type A residual current protective device is generally ad- equate. In particular cases, and depending on local factors, however, the type A residual current protective device may trip at the wrong time. For this reason, Fronius recommends that an RCD suitable for frequency con- verters be used.
  • Page 20: Connecting Solar Module Strings To The Inverter

    The power stage set, which is enclosed in a separate housing, must only be disconnected from the connection area when in a de-energized state. ▶ Maintenance and servicing in the power stage set of the inverter must only be carried out by Fronius-trained service technicians.
  • Page 21 WARNING! Danger from inadequate ground conductor connection. This can result in serious injury and damage to property. ▶ The housing screws provide a suitable ground conductor connection for grounding the housing and must NOT be replaced by any other screws that do not provide a reliable ground conductor connection.
  • Page 22: General Comments Regarding Solar Modules

    The temperature coefficients on the solar modules data sheet must be ob- served More exact values for dimensioning the solar modules can be provided by suitable calculation programs, like the Fronius Solar.creator (creator.froni- us.com). NOTE!
  • Page 23: Connecting Aluminium Cables

    Connecting alu- The DC-side terminals are suitable for connecting single-wire, round aluminium minium cables cables. Because of the formation of a non-conductive oxide layer due to the re- action of aluminium with air, the following points must be considered when con- necting aluminium cables: the reduced rated currents for aluminium cables the connection conditions listed below...
  • Page 24: Do Not Earth Solar Modules

    Do not earth sol- The inverter is designed to be connec- ar modules ted and used exclusively in conjunction with ungrounded solar modules. The solar modules must not be grounded at either the positive or negative pole. Inverter DC con- Only break out as many target break points as the number of cables that are nection provided (e.g.
  • Page 26: Cable Routing In The Dc Area

    In the case of inverters with multiple MPP trackers, there are two independent er inverters - DC inputs (MPP trackers) available. These can be connected to an unequal num- Fronius Primo ber of solar modules. 3.0 - 8.2 There are two terminals for DC+ available per MPP tracker. In total there are four terminals for DC-.
  • Page 27 Single MPP tracker mode on an inverter with multiple MPP trackers: If the strings are connected using a string collection box and only one bus is used for connection to the inverter, the connection DC+1 (pin 2) and DC+2 (pin 1) must be jumpered. The cable cross-section of the DC con- nection lead and the jumpering must be the same.
  • Page 28: Data Communication

    To cater for this eventuality, a suitable blanking cover (42,0405,2020) is available from Fronius as an option. IMPORTANT! If data communication cables are wired into the inverter, observe the following points: Depending on the number and cross-section of the data communication cables that are being introduced, take the relevant blanking plugs out of the sealing insert and insert the data communication cables.
  • Page 29 IMPORTANT! Observe the ESD guidelines when handling option cards. IMPORTANT! Only one Fronius Datamanager in master mode is permitted per Fronius Solar Net ring. Switch any other Fronius Datamanagers to slave mode or remove them. Seal off the unoccupied option card slot by replacing the cover (item number 42,0405,2094);...
  • Page 31: Australian Conduits

    Australian Conduits Tightly sealing Ensure that the conduits are tightly sealed. the conduits Seal conduits NOTE! Condensation within the conduits can damage the inverter or components of the photovoltaic systems. To avoid undesirable air circulation and condensation in the conduits: ▶...
  • Page 32: Attaching The Inverter To The Mounting Bracket

    Attaching the inverter to the mounting bracket Attaching the in- WARNING! verter to the mounting brack- Danger from inadequate ground conductor connection. This can result in serious injury and damage to property. ▶ The housing screws provide a suitable ground conductor connection for grounding the housing and must NOT be replaced by any other screws that do not provide a reliable ground conductor connection.
  • Page 34: Starting For The First Time

    Starting for the first time Starting the in- WARNING! verter for the first time Danger due to incorrect operation and incorrectly performed work. This can result in serious injury and damage to property. ▶ Only qualified personnel are authorised to commission your inverter and only within the scope of the respective technical regulations.
  • Page 35 * Country setup examples The available country setups may change during a software update. Therefore, the following list may not exactly match the display on the inverter. 50Hz International 50 Hz DE1P Deutschland (≤ 4,6 kVA) Italia ≤ 11,08 kVA 2019 60Hz International 60 Hz - cosPhi(P) 0,95 Italia >...
  • Page 37: Notes Regarding Software Updates

    Notes regarding software updates Notes regarding If the inverter is supplied with a USB software up- flash drive, the inverter software must dates be updated as soon as the inverter has been commissioned: Plug the USB flash drive into the data communication area of the in- verter Open the Setup menu...
  • Page 38: Usb Stick As A Data Logger And For Updating Inverter Software

    The file must not be deleted separately. Only delete all of the files (sys, fld, csv) at one time. DALO.fld log file: A log file for reading the data in the Fronius Solar.access software. Further details on the Fronius Solar.access software can be found in the "DATCOM Details" operating instructions at http://www.fronius.com DATA.csv log file:...
  • Page 39: Data Volume And Storage Capacity

    Structure of the CSV file: Inverter no. Inverter type (DATCOM code) Logging interval in seconds Energy in watts per second, relative to the logging interval Inductive reactive power Capacitive reactive power Average values during the logging interval (AC voltage, AC current, DC voltage, DC current) Additional information Data volume and...
  • Page 40: Buffer Memory

    ON - see the Datamanager 2.0 Operating Instructions, section "Setting and displaying the menu items", "Viewing and adjusting parameters in the DATCOM menu item"). On the Fronius Eco or Fronius Symo 15.0-3 208, the buffer memory also func- tions with just a DC supply. Suitable USB...
  • Page 41: Usb Stick For Updating The Inverter Software

    USB symbol on the inverter display, e.g. in display mode 'NOW': If the inverter detects a USB flash drive, the USB symbol will appear in the top right corner of the display. When inserting a USB flash drive, check whether the USB symbol is dis- played (it may also flash).
  • Page 42: Notes Regarding Maintenance

    Maintenance Note! When installed outdoors in a horizontal position: once a year, check that all screw joints are tight! Maintenance and servicing may only be carried out by Fronius-trained service technicians. Cleaning Clean the inverter as required with a damp cloth.
  • Page 43 Serial Number Sticker for Customer Use Serial number The serial number of the inverter is sticker for cus- located on the rating plate on the bot- tomer use tom of the inverter. Depending on the installation position of the inverter, the serial number can be difficult to access or read, e.g.