Installation - Fronius Primo GEN24 4.0 Operating Instructions Manual

Hide thumbs Also See for Primo GEN24 4.0:
Table of Contents

Advertisement

2

Installation

Danger due to insufficiently dimensioned DC cables.
Damage to the inverter due to thermal overload can result.
1
2
156
CAUTION!
When dimensioning the DC cables, adhere to the specifications in chapter
Permissible cables for the electrical connection
Disconnect connections from the solar
module strings (+/-). Switch off the
battery connected to the inverter.
Wait for the capacitors of the inverter
to discharge (2 minutes).
on page 67.
Loosen the 2 screws on the underside
of the housing cover by rotating them
180° to the left using a screwdriver
(TX20). Then lift the housing cover
away from the inverter at the bottom
and detach from above.
Loosen the 5 screws of the connection
area cover by rotating them 180° to
the left using a screwdriver (TX20).
Remove the connection area cover
from the device.