Insert the DC terminals into the re-
spective slot until they engage. Fasten
the screws of the strain-relief device to
the housing using a screwdriver (TX20)
and a torque of 1.3 – 1.5 Nm.
NOTE!
Risk due to overtorque at the strain-
relief device.
This may result in damage to the
strain-relief device.
Do not use a drill driver.
Place the cover on the connection
area. Tighten the 5 screws by rotating
them 180° to the right in the indicated
order using a screwdriver (TX20).
Clip the housing cover onto the invert-
er from above.
Press on the lower part of the housing
cover and tighten the 2 screws by ro-
tating them 180° to the right using a
screwdriver (TX20).