Camus Hydronics DynaMax DMH201 Installation And Service Manual page 52

Gas fired residential commercial stainless steel boilers
Table of Contents

Advertisement

Hold 63: LCI OFF (Flow Switch, LWCO, Blocked Flue Switch)
Hold 67: ILK OFF (Gas Pressure Switch, High Limit)
Alert 303: Abnormal Recycle: ILK off during drive to Purge
Alert 304: Abnormal Recycle: ILK off during Measured purge time
Alert 305: Abnormal Recycle: ILK off during Drive to Pre-igntion
Alert 306, 307: Abnormal Recycle: ILK off during Pre-ignition
Alert 308: Abnormal Recycle: ILK off during Main Flame
Alert 309: Abnormal Recycle: ILK off during Ignition Period
The flow switch is not closed or the low water cutoff (LWCO, optional) was tripped. This is an automatic reset error and as soon as
flow is proven this error resolves itself. To identify the safety that is open set the multimeter to Vac and measure the voltage from
one contact to ground. The contacts produce a 24Vac when the circuit is closed.
Is pump powered?
YES
Is there a current
transformer
YES
Use meter to verify
amperage draw on pump
and verify it with rating label
on pump
YES
Is there a double loop through
the current transformer?
YES
Check for contact closure
across terminals 7 and 8 on
field terminal board (perform
this step after verifying
paddle style flow switch is
operational)
YES
Check for 24Vac signal at
J5-1
NO
Check wiring between green
field terminal board and
ignition module
NO
Check pump wiring
and pump delay relay
Check operation of
NO
paddle style flow
switch installed on
outlet of DynaMax HS
Check that automatic
NO
air vent thumbscrew is
loose
Turn off power to boiler
NO
and loop Black 16 wire
twice through current
transformer
Check wiring from
current transformer or
NO
paddle flow switch to
field terminal board
Replace ignition
YES
control
YES
Purge air from water lines
Insert jumper wire
across terminals 7 and
NO
8 on field terminal
board (temporary
measure)
44