Instantaneous DHW with Brazed Plate Heat Exchanger (combination models)
Description
•
Boiler operates at a fixed
DHW setpoint
•
Modulates on boiler inlet
sensor (default)
•
Heat demand is generated
when Remote Operator is
closed.
Electrical Connection(s)
DHW Sensor, if required.
Programming Instructions
1) Place both toggle switches in LOCAL
2) Press
and select Login
3)
Select Advanced Setup
4) Select DHW Config
5) Select Demand switch = Plate Heat Exch, and Press
6) Select Mod sensor = DHW
7) Select DHW Setpoint, , and enter desired setpoint using 5-way control
8) Place right hand toggle switch setting to REMOTE for remote operation (if
required)
32