Slave Boiler
Description
Electrical Connection(s)
Programming Instructions
•
Slave boiler lead lag setup
1) Place both toggle switches in LOCAL
2) Press
and select Login
3)
Select Advanced Setup
4) Select System
5) Select System ID & Access
6) Select MB1 Modbus address = 2. To be in sequential order
7) Select MB2 Modbus address = 2. To be in sequential order
8) Select Lead Lag Config
9) Select Lead Lag Slave Config
10) Select Slave enable = Enabled via SOLA master, and Press